Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Storage temperature | Charging interval | Charging time |
-25°C-40°ºC | Every 3 months | 1 to 2 hours |
40°ºC-45°ºC | Every 2 months | 1 to 2 hours |
Model | 6KVA | 10KVA | |
Capacity | 6000VA/5400W | 10000VA/9000W | |
Input | |||
Voltage Range |
Minimum switching voltage | At 50%load,110VAC±3%;at 100%load,176VAC±3% | |
Minimum recovery voltage | Minimum switching voltage +10V | ||
Maximum switching voltage | 300VAC±3% | ||
Maximum recovery voltage | Maximum switching voltage -10V | ||
Frequency Range | 40~60HZ@50HZ system/50~70HZ@60HZ system | ||
Phase | L+N+PE | ||
Power Factor | 100%load≥0.99 | ||
Output | |||
Output Voltage | 208/220/230/240VAC | ||
Output Voltage Accuracy | ±1% | ||
Frequency Range (synchronization range) |
40~60hz@50HZsystem/50~70HZ@60HZsystem | ||
Frequency Range(battery mode) | 50hz±0.1HZor60HZ±0.1HZ | ||
Overload |
AC Mode | 30min@102%~110%load,10min@110%~130%load 30s@130%~150%load,500ms@>150%load |
|
Battery Mode | 10min@102%~110%load,1min@110%~130%load 10s@130%~150%load,500ms@>150%load |
||
Current peak ratio | 3:1(Maximum) | ||
Harmonic distortion | ≤2%(linear load),≤5%(non-linear load) | ||
Switching time | Mains(→Battery | 0ms | |
Inverter(-→Bypass | 0ms | ||
Effectiveness | |||
AC Mode | 95% | ||
Battery Mode | 94.8%(20pcs batteries) | ||
Battery | |||
Standard | Battery Number | 12-16 pCS 16 pcs | |
Charging Current | default 1A | ||
Charging Voltage | 13.65×N±1% | ||
Long Run | Battery Number | 16~20 pcS | |
Charging Current | Preset:6A±10%,1-12Aoptional | ||
Charging Voltage | 13.65×N±1% | ||
Apperance | |||
Standard | Size Long×Width×High(mm) |
384x190×730 | |
Long Run | Size Long×Width×High(mm) |
384×190×335 | |
Environment | |||
Operating Temperature | 0~40ºC | ||
Operating Moisture | <95%And no condensation | ||
Operating Altitude | <1000m** | ||
Noise | ess than 50dB@1Meter | ||
Management | |||
SmartRS-232 | Support Windows@2000/2003/XP/Vista/2008,Windows@7/8,Linux,Unix and MAC | ||
Optional SNMP | Support for power management by SNMP administrator and web browser. |
"When the output voltage is set to 208VAC,the output power will be reduced to 90%.
"If the UPS is installed and used in an environment with an altitude of more than 1000 meters,the output power should be
calculated to decelerate by 1%per 100 meters.
***Please understand that there will be no notice when product specifications are changed.
Warning Code | English Meaning | Linked Active | Triggering Conditions | Recovering Conditions |
1 | Battery is not connected |
Warning battery discharge |
Battery voltage less than 8V/PCS | Recoverable (10V/PCS) |
2 |
Low voltage in battery | Warning, battery test models return to main model | Default 11.2/pcs, Custom settings 10.5-14V/PCS(2) | Recoverable(Action point +0.2V/pcs) |
8 |
High voltage in battery |
Warning battery discharge |
Default 11.2/pcs, Custom settings +0.4V/PCS | Recoverable (Default13.7V/PCS custom settings + 0.4V/pcs) |
9 |
Chargerfailure | Warning |
After 5 minutes of charging, the battery voltage is still less than 10V |
Recoverable battery voltage more than 10.5V) |
10 |
Over-temperature warning |
Warning, battery discharge |
PFC or INV temperature sensor is higher than 80 degrees Celsius | Recoverable (The temperature sensor is below 75 degrees Celsius) |
12 | Fan failure | Warning | No fan speed signal detected | Recoverable |
13 |
Mains disconnec |
Warning |
The difference between the mains voltage and the bypass voltage is greater than 100V | Recoverable |
14 | EEPROM failure | Warning | EEPROM read and write failed | Unrecoverable |
18 | Inverter output overvoltage |
Warning, battery discharge |
load more than 102% | Recoverable (overload less than 97%) |
23 | EPO action | Warning, battery discharge |
Recoverable | |
24 | Maintenance switch action | Warning | Short circuit of CN4 terminal on control board |
Recoverable |