Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Still deciding? Get samples of US$ 926/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make at Made-in-china.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
UPS Model |
Input Breaker | Battery Fuse | Output | |||
LINE INPUT | BYPASS | M-BYPASS | Breaker | Switch | ||
10K | 32A/3P | 32A/3P | 32A/3P | 100A | 32A/3P | N/A |
15K | 50A/3P | 32A/3P | 32A/3P | 100A | 32A/3P | N/A |
20K | 50A/3P | 50A/3P | 50A/3P | 100A | 50A/3P | N/A |
30K | 63A/3P | 63A/3P | 63A/3P | 200A | 63A/3P | N/A |
40K | 100A/3P | 100A/3P | 100A/3P | 200A | N/A | 125A/3P |
60K | 100A/3P | 100A/3P | 100A/3P | 315A | N/A | 125A/3P |
80K | 125A/3P | 125A/3P | 125A/3P | 315A | N/A | 125A/3P |
100K | 225A/3P | 225A/3P | 225A/3P | 350A | 225A/3P | N/A |
120K | 225A/3P | 225A/3P | 225A/3P | 350A | 225A/3P | N/A |
160K | 350A/3P | 250A/3P | 250A/3P | 350A x 2 | 250A/3P | N/A |
200K | 350A/3P | 350A/3P | 250A/3P | 350A x 2 | 350A/3P | N/A |
UPS Model |
Line Input and Ground | BYPASS/OUTPUT | BATTERY | |||
Size (AWG) | Cross section (mm2) | Size (AWG) | Cross section (mm2) | Size (AWG) | Cross section (mm2) | |
10K | ≤ 10 | ≥ 6 | ≤ 10 | ≥ 6 | ≤ 8 | ≥ 8 |
15K | ≤ 8 | ≥ 8 | ≤ 8 | ≥ 8 | ≤ 6 | ≥ 10 |
20K | ≤ 8 | ≥ 8 | ≤ 8 | ≥ 8 | ≤ 6 | ≥ 10 |
30K | ≤ 6 | ≥ 10 | ≤ 6 | ≥ 10 | ≤ 4 | ≥ 20 |
40K | ≤ 4 | ≥ 16 | ≤ 4 | ≥ 16 | ≤ 2 | ≥ 30 |
60K | ≤ 2 | ≥ 25 | ≤ 2 | ≥ 25 | ≤ 1/0 | ≥ 50 |
80K | ≤ 1/0 | ≥ 40 | ≤ 1/0 | ≥ 40 | ≤ 3/0 | ≥ 80 |
100K | ≤ 1/0 | ≥ 40 | ≤ 1/0 | ≥ 40 | ≤ 4/0 | ≥ 100 |
120K | ≤ 3/0 | ≥ 80 | ≤ 3/0 | ≥ 80 | ≤ 4/0 | ≥ 100 |
160K | ≤ 3/0 | ≥ 80 | ≤ 3/0 | ≥ 80 | ≤ 4/0 | ≥ 100 |
200K | ≤ 4/0 | ≥100 | ≤ 4/0 | ≥100 | ≤ 4/0 | ≥100 |
LCD Screen | Parameters | Description |
Line input voltage | ||
Voltage R | Line input R to N (V) | |
Voltage S | Line input S to N (V) | |
Voltage T | Line input T to N (V) | |
Voltage RS | Line input R to S (V) | |
Voltage ST | Line input S to T (V) | |
Voltage TR | Line input T to R (V) | |
Frequency | Line input frequency (Hz) | |
Output voltage | ||
Voltage R | Load output R to N (V) | |
Voltage S | Load output S to N (V) | |
Voltage T | Load output T to N (V) | |
Voltage RS | Load output R to S (V) | |
Voltage ST | Load output S to T (V) | |
Voltage TR | Load output T to R (V) | |
Frequency | Line output frequency (Hz) | |
Output current & frequency | ||
Current R | Load output phase R current (A) | |
Current S | Load output phase S current (A) | |
Current T | Load output phase T current (A) | |
Power Factor | Load output power factor | |
R | Phase R | |
S | Phase S | |
T | Phase T | |
Output apparent Power | Load output apparent power per phase | |
R (KVA) | Phase R (KVA) | |
S (KVA) | Phase S (KVA) | |
T (KVA) | Phase T (KVA) | |
Active Power | Load output active power per phase | |
R (KW) | Phase R (KW) | |
S (KW) | Phase S (KW) | |
T (KW) | Phase T (KW) |
LCD Screen | Parameters | Description |
Total Power | Load total output power | |
KVA | Apparent power (KVA) | |
KW | Active power (KVA) | |
Connected Load in percentage | Load power percentage per phase | |
R (%) | Phase R (%) | |
S (%) | Phase S (%) | |
T (%) | Phase T (%) | |
Total Load (%) | Total connected power in percentage | |
Bypass voltage | Bypass input information | |
Voltage R | Bypass input R to N (V) | |
Voltage S | Bypass input S to N (V) | |
Voltage T | Bypass input T to N (V) | |
Voltage RS | Bypass input R to S (V) | |
Voltage ST | Bypass input S to T (V) | |
Voltage TR | Bypass input T to R (V) | |
Frequency | Bypass input frequency (V) | |
Inverter voltage | Inverter output information | |
Voltage R | Inverter output R to N (V) | |
Voltage S | Inverter output S to N (V) | |
Voltage T | Inverter output T to N (V) | |
Voltage RS | Inverter output R to S (V) | |
Voltage ST | Inverter output S to T (V) | |
Voltage TR | Inverter output T to R (V) | |
Frequency | Inverter output frequency (Hz) |
LCD Screen | Parameters | Description |
Battery and charger information | ||
Battery Voltage | Battery Voltage (V) | |
DC Bus Voltage | DC Bus Voltage (V) | |
Charging current | Charging current (A) | |
Discharging current | Discharging current (A) | |
Temperature information | ||
Control | Control board temperature (°C) | |
Battery | Battery SCR temperature (°C) | |
REC | Rectifier SCR temperature (°C) | |
INV0 | INV0 IGBT temperature (°C) | |
INV1 | INV1 IGBT temperature (°C) | |
SCR | Output SCR temperature (°C) |
LCD Screen | Parameters | Description | ||
SETTING | Basic | It's to set up basic information of the UPS. It's not relative to any function parameter. |
||
Basic | ||||
Information Advanced |
Information | The information of UPS default information and current setting of function parameters. | ||
Advanced | It's required to enter password to access the "ADVANCED" setting. |
LCD Screen | Description |
|
|
|
LCD Screen | Description |
NO: When fault occurs, UPS will remain in fault mode. |
|
If "Enable" is selected, please also set up other parameters.
Dis: Disable. When selected, UPS will alarm when related events occur.
|
LCD Screen | Description |
|
|
|
|
|
LCD Screen | Description |
|
|
High: High battery cut-off voltage.
High: Battery high loss voltage |
|
|
LCD Screen | Description |
|
LCD Screen | Description | ||||||
USER Password: 0000 |
It's required to enter password (4 digits) to access the "ADVANCED". The default password is "0000". If entered password is right, the page will jump to setting screen. If the password is wrong, it will ask to enter again. |
||||||
Disable is the default setting.
|
|||||||
OP rated voltage(V) | Low voltage point (V) |
High voltage point (V) |
220 | 165~205 (default 176) |
235~280 (default 265) |
|||
230 | 165~215 (default 176) |
245~280 (default 265) |
|||
240 | 165~225 (default 176) |
255~280 (default 265) |
|||
5. Line Frequency range: Set the acceptable line input frequency range. Low frequency point for line voltage: The setting range is 45Hz ~ 49Hz for 50Hz system and 55Hz ~ 59Hz for 60Hz system. 46Hz is default setting for 50Hz system and 56Hz is default setting for 60Hz system. High frequency point for line voltage: The setting range is 51Hz ~ 56Hz for 50Hz system and 61Hz ~ 66Hz for 60Hz system. 54Hz is default setting for 50Hz system and 64Hz is default setting for 60Hz system. |
|||||
Yes: Bypass not allowed. When selected, it's not allowed for running in Bypass mode under any situations.
DIS: Bypass disabled. When selected, no output through bypass when manually turning off the UPS.
H: High frequency point for bypass. The setting range is 51Hz ~ 56Hz for 50Hz system and 61Hz ~ 66Hz for 60Hz system. 54Hz is default setting for 50Hz system and 64Hz is default setting for 60Hz system. |
LCD Screen | Description |
High voltage point for ECO mode: The setting range is 230V ~ 264V. The default setting is 235V.
High frequency point for ECO mode: The setting range is 51Hz ~ 56Hz for 50Hz system and 61Hz ~ 66Hz for 60Hz system. The default setting is 58Hz for 50Hz system and 62Hz for 60Hz system.
Dis: Disable the auto-restart function. If selected, once UPS shutdown occurs due to running out battery and then utility restores, the UPS will not restart. |
|
High: High loss voltage. The setting range is 13V ~ 15V. The default setting value is 15V. |
These two parameters are related to the "S.D & R" on the "CONTROL" sub-menu. If executing "S.D & R" action, the UPS will shut down and restore according to system shutdown time and system restore time setting here. For example, if the system shutdown time is 1 second, the system restore time is 2min, it means the UPS will shut down in 1 minute and wait for 2 minutes, then restart again.
YES: Modify the password. If selected, the LCD will display the screen as shown in Fig. (2).
OFF: When selected, battery is not allowed charge or discharge
OFF: When selected, battery is not allowed to charge when the warning of "battery open" occurs. |
LCD Screen | Description |
It's required to enter password (4 digits) to access the "SERVICE". If entered password is right, the page will jump to service setting screen. If the password is wrong, it will ask to enter again. NOTE: please call for service to offer service password. |
|
LCD Screen | Description |
|
|
|
Battery Test: Set up battery test method.
Dis: Disable battery test timer. Default setting is disable.
Dis: Disable battery test by battery voltage. |
|
|
|
No: No change for the current password.
3-1: 3-phase in and single phase out.
|
LCD Screen | Description |
Note: In this mode, when the AC input is unstable, the UPS will enter to bypass mode. If bypass voltage is unstable or no input on bypass, there is risk of power failure for the loads. Dis: If selected, the UPS couldn't be turned on without battery.
the time from the beginning. |
|
No: It's not allowed to show real power information on "Information" menu. |
LCD Screen | Description |
|
|
|
|
|
|
|
|
|
Charging Current: Calibrate charging current setting by percentage. Charge. C. Offset: Calibrate charging current offset setting by Ampere. |
LCD Screen | Description |
ALARM W01 BATT. Open F02 BUS High |
ALARM page is used to display the current warning and fault information of the UPS. If no alarm occurs, it's blank. W means warning. Warning code and short descriptions of warning event will display. Please refer section 8.1 for the warning code. F means fault. Fault code and short descriptions of fault event will be displayed. Please refer section 8.2 for the fault code. Press "ESC" button to go back to main menu. |
LCD Screen | Description |
|
|