Symptom | Possible cause | Remedy |
No indication and alarm in the front display panel even though the mains is normal. | The AC input power is not connected well. | Check if input cable firmly connected to the mains. |
The icon and the warning code flash on LCD display and alarm beeps every second. | EPO function is enabled. | Set the circuit in closed position to disable EPO function. |
The icon and flash on LCD display and alarm beeps every second. | The external or internal battery is incorrectly connected. | Check if all batteries are connected well. |
The icon and flash on LCD display and alarm beeps twice every second. | UPS is overload. | Remove excess loads from UPS output. |
UPS is overloaded. Devices connected to the UPS are fed directly by the electrical network via the Bypass. | Remove excess loads from UPS output. | |
After repetitive overloads, the UPS is locked in the Bypass mode. Connected devices are fed directly by the mains. | Remove excess loads from UPS output first. Then shut down the UPS and restart it. | |
Fault code is shown as 43. The icon lights on LCD display and alarm beeps continuously. | UPS is overload too long and becomes fault. Then UPS shut down automatically. | Remove excess loads from UPS output and restart it. |
Fault code is shown as 14, the icon lights on LCD display, and alarm beeps continuously. | The UPS shut down automatically because short circuit occurs on the UPS output. | Check output wiring and if connected devices are in short circuit status. |
Other fault codes are shown on LCD display and alarm beeps continuously. | A UPS internal fault has occurred. | Contact your dealer |
Battery backup time is shorter than nominal value | Batteries are not fully charged | Charge the batteries at least 7 hours and then check capacity. If the problem still persists, consult your dealer. |
Batteries defect | Contact your dealer to replace the battery. | |
The icon and flash on LCD display and alarm beeps every second. | The UPS temperature is too high. | Check fans and notify dealer. |
Storage Temperature | Recharge Frequency | Charging Duration |
-25°C - 40°C | Every 3 months | 1-2 hours |
40°C - 45°C | Every 2 months | 1-2 hours |
MODEL | 6KR | 10KR | ||
CAPACITY* | 6000 VA / 4800 W | 10000 VA / 8000 W | ||
INPUT | ||||
Voltage Range | Low Line Loss | 110 VAC ± 3 % at 50% Load; 176 VAC ± 3 % at 100% Load |
||
Low Line Comeback | Low Line Loss Voltage + 10V | |||
High Line Loss | 300 VAC ± 3 % | |||
High Line Comeback | High Line Loss Voltage - 10V | |||
Frequency Range | 46Hz ~ 54 Hz @ 50Hz system 56Hz ~ 64 Hz @ 60Hz system |
|||
Phase | Single phase with ground | |||
Power Factor | >= 0.99 at 100% Load | |||
OUTPUT | ||||
Output voltage | 208/220/230/240VAC | |||
AC Voltage Regulation | ± 1% | |||
Frequency Range (Synchronized Range) |
46Hz ~ 54 Hz @ 50Hz system 56Hz ~ 64 Hz @ 60Hz system |
|||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | |||
Overload | AC mode | 100%~110%: 30min; 110%~130%: 5min; >130% : 10sec | ||
Battery mode | 100%~110%: 3min; 110%~130%: 30sec; >130% : 10sec | |||
Current Crest Ratio | 3:1 max | |||
Harmonic Distortion | <= 3 % THD (Linear Load) <= 5 % THD (Non-linear Load) |
|||
Transfer Time | Line Battery | 0 ms | ||
Inverter Bypass | 0 ms | |||
EFFICIENCY | ||||
AC mode | > 92% | > 93% | ||
Battery Mode | > 90% | > 91% | ||
BATTERY | ||||
Standard Model | Type & Numbers | 12 V / 9 Ah x 16 | ||
Recharge Time | 9 hours recover to 90% capacity | |||
Charging Current | Default : 1 A ± 10% Max.: 1A, 2A (Adjustable) |
|||
Charging Voltage | 218.4V ± 1% | |||
Long-run Model | Type | Depending on applications | ||
Numbers | 16 | |||
Charging Current | Default: 4 A ± 10% Max.: 1A, 2A, 4A, 6A (Adjustable) |
|||
Charging Voltage | 218.4V ± 1% | |||
PHYSICAL | ||||
Standard Model | Dimension,DXWXH(mm) | UPS unit: 500 x 438 x 88 [2U] Battery pack: 668 x 438 x 88 [2U] |
UPS unit: 580 x 438 x 88 [2U] Battery pack: 668 x 438 x 88 [2U] |
|
Net Weight (kgs) | UPS unit: 15 Battery pack: 48 |
UPS unit: 18 Battery pack: 48 |
||
Long-run Model | Dimension, DXWXH(mm) | 500 x 438 x 88 [2U] | 580 x 438 x 133[3U] | |
Net Weight (kgs) | 15 | 18 | ||
ENVIRONMENT | ||||
Operation Temperature | 0 ~ 50°C (battery life cycle will be shorten when temperature is above 25°C) |
0 ~ 40°C (battery life cycle will be shorten when temperature is above 25°C) |
||
Operation Humidity | <95 % and non-condensing | |||
Operation Altitude** | <1000m | |||
Acoustic Noise Level | Less than 55dB @ 1 Meter | Less than 58dB @ 1 Meter | ||
MANAGEMENT | ||||
Smart RS-232 or USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC | |||
Optional SNMP | Power management from SNMP manager and web browser |