Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make at Made-in-china.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | Wall-mounted type | Vertical type | |||||
1KVA | 2KVA | 3KVA | 1KVA | 2KVA | 3KVA | ||
Capacity | 1KW | 2KW | 3KW | 1KW | 2KW | 3KW | |
Input | |||||||
Voltage Range |
Minimum switching voltage | At 50% load, 11OVAC +3%; at 100% load, 176VAC+3 % | |||||
Minimum recovery voltage | Minimum switching voltage +10V | ||||||
Maximum switching voltage | 300VACI3 % | ||||||
Maximum recovery voltage | Maximum switching voltage -10V | ||||||
Frequency Range | 40-60HZ@50HZ system/50-70HZ@60HZ system | ||||||
Phase | L+ N+PE | ||||||
Power Factor | 100% load z0.99 | ||||||
Output | |||||||
Output Voltage | 208/220/230/240VAC | ||||||
Output Voltage Accuracy | I1% | ||||||
Frequency Range (synchronization range) |
40-60hz@50HZsystem/50-70HZ@60HZsystem | ||||||
Frequency Range (battery mode) | 50hz+0.1 HZor60HZ+0.1 HZ | ||||||
Overload |
AC Mode | 30min@102%-110%Ioad, 10min@110%-130%load 30s@130%-150%Ioad, 500ms@>150 %Ioad | |||||
Battery Mode | 10min@102%-110%Ioad, 1min@110%-130%load 10s@130%-150%Ioad, 500ms@> 150 %Ioad | ||||||
Current peak ratio | 3:1 (Maximum) | ||||||
Harmonic distortion | 2% ( linear load ) , 5%(non-linear load) | ||||||
Switching time | Mains Battery | Oms | |||||
Inverter Bypass | 0ms | ||||||
Effectiveness | |||||||
AC Mode | 95% | ||||||
Battery Mode | 94.8% (20pcs batteries) | ||||||
Battery | |||||||
Standard |
Battery Number | 2 pcs | 4 pcs | 6 pcs | 2 pcs | 4 pcs | 6 pcs |
Charging Current | default 1A | ||||||
Charging Voltage | 13.65 x NI1 % | ||||||
Long Run |
Battery Number | 3 pcs | 6 pcs | 8 pcs | 3 pcs | 6 pcs | 8 pcs |
Charging Current | Preset: 6A110%, 1-12A optional | ||||||
Charging Voltage | 13.65x N*1% | ||||||
Apperance | |||||||
Standard | Size Long Width High(mm) |
310"438"88 | 380"438"88 | 506"438"88 | 284"145"213 | 398"145"213 | 450"192"335 |
Long Run | Size Long Width High(mm) |
310"438"88 | 380"438"88 | 380"438"88 | 284"145"213 | 398"145"213 | 398"145"213 |
Environment | |||||||
Operating Temperature | 0-40°C | ||||||
Operating Moisture | < 95%And no condensation | ||||||
Operating Altitude | < 1000m"" | ||||||
Noise | less than 50dB@1Meter | ||||||
Management | |||||||
SmartRS-232 | Suppon Windows@2000/2003/XP/Vista/2008. Windows@7/8, Linux. Unix and MAC | ||||||
Optional SNMP | Support for power management by SNMP administrator and web browser. |
Warning Code | English Meaning | Linked Active | Triggering Conditions | Recovering Conditions |
1 |
Battery is not connected | Warning, battery discharge |
Battery voltage less than 8V/PCS | Recoverab Ie(10V/PCS) |
2 |
Low voltage in battery | Warning, battery test models return to main model | Default 11.2/pcs, Custom settings 10.5-14V/PCS(2) | Recoverable (Action point +0.2V/pcs) |
3 |
Charging short circui | Warning, No charging to batteries |
The battery voltage is lower than 5V/pcs,current is more than 4A | Unrecoverab ie |
4 |
Mains L/N reverse connectionor the groundwire is not connected |
Warning |
Hardware trigger |
Reco nn ect the L/ N of the ma in s powe r afte r powe r fa iIure , ch eck wheth er the gro u nd wire is con n ected , or send a co mm u n icatio n com ma n d to p ro hi b it L/N reverse conn ecti o n |
8 |
High voltage in battery |
Warning, battery discharge |
Default 11.2/pcs, Custom settings +0.4V/PCS |
Recoverable (DefauIt13.7V /PCS,custom settings +0.4V /pcs) |
9 |
Chargerfa ilure |
Warning |
After 5 minutes of charging, the battery voltage is still less than 10V | Recoverable (battery voltage more than 10.5V) |
10 |
Over-temperature warning |
Warning, battery discharge |
PFC or INV temperature sensor is higher than 80 degrees Celsius | Recoverab ie (The temperature sensor is below 75 degrees C elsius) |
12 | Fan failure | Warning | No fan speed signal detected | Recoverable |
13 |
Mains disconnect |
Warning |
The difference between the mains voltage and the bypass voltage is greater than 100V | Recoverable |
14 | EEPROM failure | Warning | EEPROM read and write failed | Unrecoverable |
18 |
Inverter output overvoltage | Warning, battery discharge |
load more than 102% |
Recoverable (overload less than 97%) |
22 |
Overload lock in bypass | Warning |
3 times of overload transfer to bypass mode in 30 minutes | Manual boot can be restored |
23 | EPO action | Warning, battery discharge |
Recoverable | |
24 | Maintenance switch action | Warning | Short circuit of CN4 terminal on control board | Recoverable |
Fault code | English meaning | Related actions | Trigg er condition | Recovery condition |
1 | Busbar boost soft start failure | Turn to fault mode | When the busbar starts soft, the 30S cannot reach 380V | Unrecoverable |
2 | Busbar over voltage | Turn to fault mode | When the busbar is above 450V,it will lasts 5s | Unrecoverable |
3 | Busbar und ervoltage | Turn to fault mode | When the busbar is below 200V, it will lasts 400ms | Unrecoverable |
4 | DC boost failure | Turn to fault mode | DC-DC hardware protection that triggered the exception | Unrecoverable |
g | Battery relay short circuit | Turn to fault mode | Battery voltage is greater than 310V and lasts for 4s | Unrecoverable |
9 | Busbar soft start relay failure | Turn to fault mode | The bus relay is still below SOV after 5s soft start | Unrecoverable |
10 | Bus bar short circuit | Turn to fault mode | During normal operation, the mother is instantaneously below 180V | Unrecoverable |
17 |
Inverter soft StaFt failure |
Turn to fault mode |
After inverting soft start 40s, the rated output voltage cannot be reached, or after inverting soft 2s, the inverter voltage is still less than 20V. | Unrecoverable |
18 | Inverter output overvoltage | Turn to fault mode | The inverter voltage is higher than 276V and lasts 400ms | Unrecoverable |
19 | Inverter output undervoltage | Turn to fault mode | The inverter voltage is below 130V and lasts 400ms | Unrecoverable |
20 | Inverter short circuit | Turn to fault mode | The inverter voltage is less than SOV, the current is hipher than 20A, andlasts 4s | Unrecoverable |
26 | Negative power protection | Turn to fault mode | Inverter power is less than -2400W for 20ms, or -800W for 120ms | Unrecoverable |
33 |
Inverter relay open | Turn to fault mode |
When the inverter relay is cIosed,the difference between the inverter voltage andthe output voltage exceeds 30V for 160ms | Unrecoverable |
34 |
Inverter rela short circuity |
Turn to fault mode |
When the bypass relay is cIosed,the inverter relay is disconnected and the inverter bridge is not working the difference between the inverter voltage and the bypass voltage is less than 30V |
Unrecoverable |
35 |
Bypass FBIay open | Turn to fault mode |
When the bypass relay is cIosed,the difference between the bypass voltage and the output voltage exceeds 30V for 160ms | Unrecoverable |
36 |
Bypass relay short circuit |
Turn to fault mode |
When the bypass relay and the inverter relay are disconnected,the difference etween the output voltage and the bypass voltage is less than 30V for 160ms |
Unrecoverable |
37 |
Input and O t Ut reversed 'J p | Turn to fault mode |
When the bypass relay and the inverter relay are disconnected,the bypass voltage is less than 20V, but the output voltage is greater than 150V | Unrecoverable |
39 | Charger short circuit | Turn to fault mode | The battery voltage is less than SOV and the charging current is higher than 4A | Unrecoverable |
66 | Overload fault | Turn to fault mode | The load exceeds the specification | Unrecoverable |
67 | Reverse battery | Turn to fault mode | The battery input is reversed | Unrecoverable |
68 | Model recognition error | Turn to fault mode | Undefined machine model | Unrecoverable |
73 | No bootloader | Turn to fault mode | No boot program | Unrecoverable |